Select your cable size from the left-hand columns to determine maximum capacity of pathways.

Cable Diameter Pathway Cable Capacity
mm inches EZD22
Series
EZD33
Series
EZD44+
Series
3 0.118 70 368 868
3.5 0.138 54 266 648
4 0.157 35 204 483
4.5 0.177 28 165 399
5 0.197 24 130 323
5.5 0.216 20 108 255
6 0.236 15 88 210
6.5 0.256 12 70 182
7 0.275 12 63 156
8 0.314 6 48 110
9 0.354 6 35 90
12.5 0.491 2 20 42
15 0.590 2 12 30
18 0.708 1 6 20
20 0.786 1 6 16
25 0.983 0 4 9
30 1.179 0 2 6
35 1.376 0 2 4

Use this quick and easy calculator to figure out the size and number of EZ-Path sleeves required for each barrier penetration.

NOTE: This calculator assumes use of cable installation practices that maximize pathway utilization. The calculated results should be considered the minimum required. Download Maximize EZ-Path Capacity to identify additional factors that may influence the number of pathways required for your installation.

1. Select your cable size by clicking the cable diameter at left.

2. Enter the number of cables you will be installing now.

3. Enter a value for cables you may be adding in the future.

Cable Diameter: Choose from column at left
 
Cables to be installed:

CABLES NOW

CABLES FUTURE
 
Pathways Required:

TOTAL CABLES

EZD22

EZD33

 

EZD44+

Pathway Capacity Chart
(Pathway Cable Capacity Chart)

IMPORTANT NOTICE:The information herein is theoretical and is provided for informational purposes only. Variations in cable size and shape, as well as cable bundle size and other factors may influence these calculations. Therefore, THE ACCURACY OF THIS INFORMATION CANNOT BE GUARANTEED.

U.S. Patent 6,732,481